Flowlink Cipher : Flowlink Cipher : Analysis : Graph View : Error Codes for Data Points
 

Error Codes for Data Points

The table below provides a list of possible error codes that a device may have assigned to a data point that was ingested into a dataset in the system. These codes are included in the tooltip displayed when the mouse cursor is hovered over a point in a graph if that point has been assigned a code. They are also included in the data table that can be displayed for graphs.

Error Code

 

Model/Device

 

4100, 4200, 6700

2100

300

301

304

307

308

310

310 EX

330

350

360

360 EX (Firmware 3.0 and above)

310

360

Other

No Data 1

Failed Measurement/missing sensor

Failed Measurement/missing sensor

Failed Measurement/missing sensor

Failed Measurement/missing sensor

Failed Measurement/missing sensor

Failed Measurement/missing sensor

Over Heating

Failed Measurement/missing sensor

Signal Strength too Low

Failed Measurement/missing sensor

Failed Measurement/missing sensor

Low Power

Signal Strength too Low

Doppler Power too low / No Peak detected

n/a

No Data 2

Value out of range

Value out of range

Value out of range

Value out of range

Value out of range

Value out of range

Slew Active Error

Value out of range

n/a

Value out of range HIGH

Undefined

Flow Direction Error

n/a

Can't determine direction / Too slow

n/a

No Data 3

Interpolated Value - velocity

Interpolated Value - velocity

Undefined

Undefined

Undefined

Undefined

Undefined

Undefined

No Repsonce from the sensor

Value out of range LOW

Velocity Filter Error

Ultrasonic Error

No Repsonce from the sensor

Level too low

n/a

No Data 4

Level too low / Zero Flow on Error active - Velocity

Level too low / Zero Flow on Error active - Velocity

Undefined

Undefined

Undefined

Undefined

Current Fault

Undefined

n/a

Plugged Bubble Line

Undefined

ADC Reading Error

n/a

Signal too noisy

n/a

No Data 5

n/a

n/a

Undefined

Undefined

Undefined

Undefined

Undefined

Undefined

n/a

Pump Pressure Error (Run time too long)

Velocity Gain Error

Laser Focus Error

n/a

Focus error

n/a

No Data 6

n/a

n/a

Undefined

Undefined / Calibration

Undefined

Undefined

Undefined

Undefined

n/a

Pump Motor Error (Current draw out of range)

Level too low

Sensor Com Failure

n/a

DSP Com Error

n/a

No Data 7

n/a

n/a

Measurement Timeout / sensor not responding

Measurement Timeout / sensor not responding

Measurement Timeout / sensor not responding

Measurement Timeout / sensor not responding

Measurement Timeout / sensor not responding

Measurement Timeout / sensor not responding

Measurement Timeout / sensor not responding

Measurement Timeout / sensor not responding

Measurement Timeout / sensor not responding

Measurement Timeout / sensor not responding

Measurement Timeout / sensor not responding

Measurement Timeout / sensor not responding

Measurement Timeout / sensor not responding

No Data 8

n/a

n/a

n/a

n/a

n/a

n/a

n/a

n/a

n/a

n/a

n/a

n/a

n/a

No level from 310.

n/a

Error Code

Model/Device

4100, 4200, 6700, 700 Modules

255

Clock Changed

254

Power Fail

253

Input Error

252

Record Deleted

251

Gap Record

250

Data Overflow

249

Not Measured

248

Velocity Error

247

Level below min